EYR 10*1.5RE//5

Description

Description

Standards

  • Product
    IEC 60228; IEC 60502-1
  • Test
    IEC 60332-1-2

Scope

This specification covers PVC insulated, multicore armoured cables, rated at 0.6/1 KV to international standard IEC 60502-1 for use indoors, outdoors, in cable ducts and for direct burial underground, where severe mechanical stresses are present.

Construction

2.1 Conductor

Plain, annealed copper conductors, circular stranded, or sectoral stranded, conforming to the applicable requirements of IEC 60228.

2.2 Insulation

PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.

2.3 Assembly

Insulated conductors are laid up, filled where necessary with non-hygroscopic material and covered with an extruded thickness of thermoplastic material.

2.4 Armour

Galvanized round wires, completely covering the assembly of cores; complying to the applicable requirements of IEC 60502-1.

2.5 Sheath

PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.

TEST AT WORKS according to IEC 60502-1 armored

 Routine Tests                                                              

- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2  

- Voltage test acc. to IEC 60502-1  parag. 15.1 & 15.3 

                                                                       

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided. 

                                                                       

Sample Tests                                                              

            - Check of the build - up and color coding of the cable 

            - Check of dimensions 

                        Insulation:         according to IEC 60502-1                       Parag.  16.5.2

                        Armour:             according to IEC 60502-1                       Parag.  16.7

                        Oversheath:      according to IEC 60502-1                       Parag.  16.5.3

                                                                       

These tests will be carried out on one length of each size during each inspection . 

Tests certificates will be provided by Liban Cables 

                                                                       

Type Tests                                                                  

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.  

These tests will be carried out on one length of the order . 

Tests certificates will be provided by Liban Cables

Cable identification - LV cables ≤ 1KV

INSULATION COLORS:   

 

Neutral

Cond.1

Cond.2

 Cond.3

Cond.4

1 Conductor

 

BLACK

 

 

 

2 Conductors

GREY

BLACK

 

 

 

3 Conductors

 

BLACK

RED

BLUE

 

4 Conductors

GREY

BLACK

RED

BLUE

 

5 Conductors

GREY

BLACK

RED

BLUE

GREEN

 

All numbered control cables (6 conductors and above), are insulated with white color, and numbered with black digits

 

CABLE MARKING OVER THE OUTER JACKET  (by inkjet printing):

LIBAN CABLES     DESCRIPTION     RATED VOLTAGE     SECTION MM2     Year of manufacture     meter marking

 

Other cable identification requirements are available upon request

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor flexibility
Solid class 1
Conductor shape
Circular solid (RE)
Insulation
PVC
Armour type
Galvanized steel wires
Outer sheath
PVC

Dimensional characteristics

Dimensional characteristics

Number of cores
10
Conductor cross-section
1.5 mm²
Nominal insulation thickness
0.8 mm
Nominal armour wire diameter
1.25 mm
Nominal outer sheath thickness
1.8 mm
Nominal overall diameter
19.5 mm
Approximate weight
710 kg/km

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
12.1 Ohm/km
Permissible current rating in open air
20 A
Permissible current rating when buried
30 A
Rated Voltage Uo/U (Um)
0,6/1 kV
Test voltage
3500 V

Usage characteristics

Usage characteristics

Ambient air temperature
30 °C
Flame retardant
IEC 60332-1-2
Installation temperature, range
-5 ... 50 °C
Maximum operating temperature
85 °C
Operating temperature, range
-15 ... 55 °C
Short-circuit max. conductor temperature
160 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close